Description
Centralised steam distributors
is such that during humidification in the air duct and air conditioner, the steam temperature is reduced by a maximum of 2 degrees Celsius. As a result, there is very little condensation. The abbreviation SAM (Short Absorption Manifold) means absorption of vapor at a short distance by passing air. Which avoids getting wet in the walls of the humidifying place and wasting steam.
All metal parts of the distributor are made of 304 steel to ensure full compliance with health regulations and long life. The system is easily installed in the air duct with a short length. By installing the ir33 series universal humidity control unit and ambient relative humidity sensor or duct curl and BELIMO two-way steam control valve, you will be able to accurately adjust the passing steam flow.
Humidity profile of centralized steam distributor
Condensate water separator
In this system, the inlet manifold acts as a condensate water separator. The concave curvature of the pipe causes the steam to flow in a certain direction and the condensed water exits from its discharge point. In this way, only dry steam can pass through the pipe.
Condensate water separator
Insulation of pipes
Tubes are ordered with air cushions. A structure made of AISI 304 steel protects the steam pipe from direct contact with air from the duct/air conditioner. And cause a 30% reduction in the amount of condensate is.
Insulation of pipes in the central steam distributor
Anti-condensation nozzles
To achieve the shortest steam absorption distance in the air conditioner and ensure that only dry steam is transferred to the duct, the pipes are equipped with nozzles. These nozzles receive steam from inside the pipe, not from the walls where there is a possibility of condensation.
Anti-condensation nozzles